Stuart-turner Techflo TP 60TNH Manuel d'utilisateur Page 8

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 28
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 7
- 8 -
Cont ...
2.32 Non-preferred pump location: If it is not possible to locate the pump in the
preferred area due to site limitations and it is necessary to position the unit in the
loft, or in a position above the secondary tapping that feeds the pump, then there
is an increased risk of air locks. This risk must be eliminated.
The following measure is a suggestion that may overcome the problem:
In this application only use an Essex or Techflow side entry flange, then fit a “U”
bend or downward loop in the supply pipe to the pump of 350 mm depth before
rising to the pump should ensure the cylinder vents its air up the expansion pipe,
not up the pump feed (Figs. 6 & 7).
Max. inlet head 6 m
Min. inlet head 0.5 m
hot water
services
Negative
head
200 mm
min
350 mm
Max. outlet head 6 m
least preferred area
Fig. 7 - Twin Pump
Max. inlet head 6 m
Min. inlet head 0.5 m
Negative
head
200 mm min
350 mm
min
Max. outlet head 6 m
least preferred
area
Fig. 6 - Single Pump
Vue de la page 7
1 2 3 4 5 6 7 8 9 10 11 12 13 ... 27 28

Commentaires sur ces manuels

Pas de commentaire